dc.identifier.urihttp://dx.doi.org/10.18419/opus-12744-
dc.description.abstractPhase resolved partial discharge patterns (PRPD) are routinely used to assess the condition of power transformers. In the past, classification systems have been developed in order to automate the fault identification task. Most of those systems work with the assumption that only one source is active. In reality, however, multiple PD sources can be active at the same time. Hence, PRPD patterns can overlap and cannot be separated easily, e.g., by visual inspection. Multiple PD sources in a single PRPD represent a multi-label classification problem. We present a system based on long short-term memory (LSTM) neural networks to resolve this task. The system is generally able to classify multiple overlapping PRPD by while only being trained by single class PD sources. The system achieves a single class accuracy of 99% and a mean multi-label accuracy of 43% for an imbalanced dataset. This method can be used with overlapping PRPD patterns to identify the main PD source and, depending on the data, also classify the second source. The method works with conventional electrical measuring devices. Within a detailed discussion of the presented approach, both its benefits but also its problems regarding different repetition rates of different PD sources are being evaluated.en
dc.description.sponsorshipDeutsche Forschungsgemeinschaftde
dc.language.isoende
dc.relation.uridoi:10.3390/en14082144de
dc.rightsinfo:eu-repo/semantics/openAccessde
dc.rights.urihttps://creativecommons.org/licenses/by/4.0/de
dc.subject.ddc621.3de
dc.titleClassification of superimposed partial discharge patternsen
dc.typearticlede
dc.date.updated2021-05-03T11:56:34Z-
ubs.fakultaetInformatik, Elektrotechnik und Informationstechnikde
ubs.institutInstitut für Energieübertragung und Hochspannungstechnikde
ubs.publikation.seiten10de
ubs.publikation.sourceEnergies 14 (2021), No. 2144de
ubs.publikation.typZeitschriftenartikelde
Enthalten in den Sammlungen:05 Fakultät Informatik, Elektrotechnik und Informationstechnik

Dateien zu dieser Ressource:
Datei Beschreibung GrößeFormat 
energies-14-02144.pdf1,33 MBAdobe PDFÖffnen/Anzeigen


Diese Ressource wurde unter folgender Copyright-Bestimmung veröffentlicht: Lizenz von Creative Commons Creative Commons