Frequency range of UHF PD measurements in power transformers

dc.contributor.authorTenbohlen, Stefan
dc.contributor.authorBeura, Chandra Prakash
dc.contributor.authorSikorski, Wojciech
dc.contributor.authorAlbarracín Sánchez, Ricardo
dc.contributor.authorAlbuquerque de Castro, Bruno
dc.contributor.authorBeltle, Michael
dc.contributor.authorFehlmann, Pascal
dc.contributor.authorJudd, Martin
dc.contributor.authorWerner, Falk
dc.contributor.authorSiegel, Martin
dc.date.accessioned2023-03-02T15:27:54Z
dc.date.available2023-03-02T15:27:54Z
dc.date.issued2023de
dc.date.updated2023-02-23T10:19:37Z
dc.description.abstractAlthough partial discharge (PD) measurement is a well-accepted technology to assess the quality of the insulation system of power transformers, there are still uncertainties about which frequency range PDs radiate and which frequency range should be evaluated in a measurement. This paper discusses both a UHF PD frequency range obtained from studies investigating laboratory experiments and a frequency range from numerous practical use cases with online and on-site measurements. The literature review reveals a frequency spectrum of ultrahigh-frequency (UHF) PD measurements in the range of 200 MHz to 1 GHz for most publications. Newer publications extend this range from 3 to 6 GHz. The use cases present UHF PD measurements at transformers with power ratings up to 1000 MVA to determine frequency ranges which are considered effective for practical applications. The “common” frequency range, where measurements from all use cases provide signal power, is from approximately 400 MHz to 900 MHz, but it is noted that the individual frequency range, as well as the peak UHF signal power, strongly varies from case to case. We conclude from the discussed laboratory experiments and practical observations that UHF PD measurements in power transformers using either valve or window antennas, according to Cigré, are feasible methods to detect PD.en
dc.identifier.issn1996-1073
dc.identifier.other1838455752
dc.identifier.urihttp://nbn-resolving.de/urn:nbn:de:bsz:93-opus-ds-127951de
dc.identifier.urihttp://elib.uni-stuttgart.de/handle/11682/12795
dc.identifier.urihttp://dx.doi.org/10.18419/opus-12776
dc.language.isoende
dc.relation.uridoi:10.3390/en16031395de
dc.rightsinfo:eu-repo/semantics/openAccessde
dc.rights.urihttps://creativecommons.org/licenses/by/4.0/de
dc.subject.ddc621.3de
dc.titleFrequency range of UHF PD measurements in power transformersen
dc.typearticlede
ubs.fakultaetInformatik, Elektrotechnik und Informationstechnikde
ubs.fakultaetFakultätsübergreifend / Sonstige Einrichtungde
ubs.institutInstitut für Energieübertragung und Hochspannungstechnikde
ubs.institutFakultätsübergreifend / Sonstige Einrichtungde
ubs.publikation.seiten21de
ubs.publikation.sourceEnergies 16 (2023), No. 1395de
ubs.publikation.typZeitschriftenartikelde

Files

Original bundle

Now showing 1 - 1 of 1
Thumbnail Image
Name:
energies-16-01395-v2.pdf
Size:
7.63 MB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
3.39 KB
Format:
Item-specific license agreed upon to submission
Description: